LSF/LSOH Wires and cables
These are the low smoke halogen-free wires & cables, essential used in residential & commercial buldings, public areas, railway platforms where human life safety & evacuation, less damage to property during fire situation is important. Voltage range includes 450/750 V, 0.6/1.0 kV & 1.8/3.0 kV. Cables are mostly manufactured to BS & IEC standard.
LSF/LSOH WIRES
Construction
Annealed Plain Copper Conductor
LSF/LSOH Insulation
Properties
– Flame retardant to IEC 60332-1
– Low smoke emission to IEC 61034-1 & 2, light transmittance 60%↑
– Halogen acid gas test to IEC 60754-1 & 2, halogen content 0.5%↓
Product Range – 1.5 to 630 mm 2
Type Tested By – BSI
Application
For places where self-extinguishing behaviour, toxic & corrosive gases free and reduced smoke emission level cables are required for safety.
Type – H07Z-R, H07Z-K, H07Z-U
Rated Voltage – 450/750 V
Applicable Standards – BS EN 50525-3-41 (previously BS 7211)
Operating Temperature – 90°C
LSF/LSOH CABLES
Construction
Annealed Plain Copper Conductor
XLPE Insulation
Armoured or Unarmoured
LSF/LSOH Outer Sheath
Applicable Standards
BS 6724 / IEC 60502‐1
Operating/Short Circuit Temperature – 90°C / 250°C
Product Range
– 1 core – 50 to 1000 mm2
– 2 core & 5 core – 1.5 to 120 mm 2
– 3 core & 4 core – 1.5 to 400 mm 2
– Above 5 core to 48 Cores – 1.5 to 4 mm 2
Type Tested By – BSI
Application
For places where self-extinguishing behaviour, toxic & corrosive gases free and reduced smoke emission level cables are required for safety.
Rated Voltage
– 0.6/1.0 (1.2) kV
– 1.8/3 (3.6) kV
Properties
– Flame retardant to IEC 60332-3/Cat.A
– Low smoke emission to IEC 61034-1 & 2, light transmittance 70%↑
– Halogen acid gas test to IEC 60754-1 & 2, halogen content 0.5%↓