Lightning Protection block GZ-1-35
The lightning protection unit GZ-1-35 must be installed in the immediate vicinity of the UKZ.
The GZ-1-35 block must be reliably grounded.
The GZ-1-35 block is installed in series between the output of the UKZ and the pipeline. In case of overvoltage in the pipeline, the unit diverts current to the ground to 20 kA and lowers the voltage at the output terminals of the UKZ to 56 V.
Technical characteristics of the lightning protection unit GZ-1-35
Parameters of the transmitted signal:
- voltage: no more than 92 V
- current: no more than 35 A
Surge Protection Parameters:
- protection voltage: no more than 150 V
- discharge current (8 / 20mks): no more than 20 kA
Permissible reverse voltage: 1200 V
Ambient temperature: from minus 45 ° С to +50 ° С
Relative humidity: 95% at a temperature of +25 ° C
Overall dimensions: 397х265х141 mm
Weight: 5.0 kg