Device for Controlling gas fire Extinguishing Installations (AIST)
PPKPU 4/16 provides the following types of fire protection:
- Modular automatic fire extinguishing systems;
- Centralized automatic fire extinguishing installations;
- Fire alarm;
- Combined type of protection.
The device is built on a functional-modular address structure and consists of PPKPU 4/16 and functional addressable devices.
Each addressable device is connected to the signal lines of communication PPKPU 4/16 and performs strictly defined functions.
Addressable devices PPKPU 4/16:
UPT fire extinguishing device - performs the functions of protecting one zone, both in modular and centralized automatic fire extinguishing installations. It controls 3 loops of a fire alarm, a weighing device, a pressure switch, buttons for restoring automatic mode and remote start, the door position of the protected room. Manages the launch of a modular fire extinguishing installation, light and sound warning and engineering equipment, in accordance with the fire extinguishing algorithm;- Station device UST - performs the control functions of 8 fire-extinguishing station start-up devices, with the possibility of their configuration for organizing the output of the necessary mass of extinguishing agent in a given direction, monitoring the weight device and pressure gauge in central fire extinguishing installations;
- Remote control device UDU - performs the functions of controlling switchgears in centralized fire extinguishing installations or controlling engineering equipment in a fire alarm system;
- UPS fire alarm device - performs the functions of a fire alarm. It controls 4 fire alarm loops.
Product Specifications
The number of fire alarm loops controlled by the device - up to 256
The number of protected fire extinguishing zones controlled by the device - up to 16
Degree of protection of a cover - IP 54
The device is resistant to external electromagnetic interference of 3 degrees of rigidity according to GOST R 50009 and NPB 57-97 and the level of generated radio interference corresponds to class "B" according to GOST R 51318.22.
Power supply of PPKPU 4/16 is carried out from the alternating current main - 220 (-33 / + 22) V and with a frequency (50 ± 1) Hz;
Power supply for addressable devices is provided from PPKPU 4/16 or from an additional backup power source. The voltage of the addressable devices is 24 ± 4 V.
Overall dimensions of PPKPU and address devices:
PPKPU | 360x280x139 mm |
Oops | 210x131x74 mm |
UPT | 344x260x112 mm |
UDU | 210x131x74 mm |
TSI | 331x260x112 mm |
Weight of control panel and addressable devices:
PPKPU | 7.0 kg |
Oops | 1,5 kg |
UPT | 5.0 kg |
UDU | 1,5 kg |
TSI | 5.0 kg |
PPKPU 4/16 meets the requirements of the Technical Regulation on fire safety requirements (Federal Law No. 123-F3 of 07.22.2008) and GOST R 53325.
PPKPU 4/16 meets the requirements of the Technical Regulations of the Customs Union:
- TR TS 004/2011 “On the safety of low-voltage equipment”
- TR TS 020/2011 "Electromagnetic compatibility of technical means"
PPKPU 4/16 is certified in the first category of seismic resistance according to NP-031-01, as well as in safety class 3H according to NP-001-15 with seismic effects of 9 points and MP3 according to the MSK-64 scale when installed above the zero mark up to 70 m inclusive .
An example of an entry of PPKPU 4/16 and address devices when ordering:
- Fire alarm control panel PPKPU 4/16 "AIST"
- UPS fire alarm device
- UPT fire extinguishing device
- Device station UST
- Remote Control Device