Complete transformer substations (KTP) block-type for voltage of 35 and 110 kV are designed for reception, transformation, distribution and transit of electric energy of three-phase alternating current of industrial frequency of 50 Hz at nominal voltages of 110 and 35 kV.
概观:
Parameter name Parameter value
KTPB 110 KTPB 35
Maximum power, kVA, no more than 63000 63000
Number of power transformers 1, 2
Type of switchgear ORU; ZRU
Group of connections of power transformers in accordance with GOST R 52719 Yн/Yн/Δ-0-11 1)
Insulation level in accordance with GOST 1516.3 a, b
Test voltage of insulation of electrical equipment of the KTPB in a dry state for one minute in accordance with the requirements of GOST 1516.3, kV
- electrical equipment relative to the ground 230 80/95 2)
- power transformers relative to earth 200 80/95 2)
- between the contacts of the fuse disconnectors 230 95/120 2)
Test voltages for checking the electrical strength of insulation of auxiliary circuits for 1 min in accordance with GOST 1516.3, kV 2 3)
Specific area, m2/(kVA), no more than 0,020 0.044
Specific gravity, kg/(kVA), not more than 0.496 1,030
Collection coefficient, not less than 0.78 0.7

VN side

Nominal voltage, kV 110 35
Maximum working voltage, kV 123 40.5
Rated current of main circuits, A 630, 1000, 2000
Nominal current of busbars, A 630, 1000, 2000
Electrodynamic withstand current of busbar, kA 80; 100; 125 50; 63; 80
Thermal withstand current of busbar for 3 s, kA 25; 31.5; 40; 50 20; 25; 31.5
Type of regulation on the HV side RPN
Type of current of auxiliary circuits Variable, constant
Nominal voltage of auxiliary circuits, V 380±19; 220±11
Frequency of alternating current of auxiliary circuits, Hz 50
Insulation resistance, MOhm 500
Leakage path length along external insulation, cm/kV not less than 2.25
Input/output execution air

Side NN

Type of switchgear KRU
Nominal voltage, kV 6;10
Maximum working voltage, kV 7.2; 12
Frequency of alternating current of main circuits, Hz 50
Rated current of main circuits, A 400; 630; 1000; 1250; 1600; 2000; 2500; 3150
Nominal current of busbars, A 400; 630; 1000; 1250; 1600; 2000; 2500; 3150
Thermal withstand current for 3 s, Ik, kA 20; 31.5; 40
Rated breaking current of the circuit breaker, kA 12.5; 20; 25; 31.5; 40
Rated current of electrodynamic withstand of main circuits, kA 32; 51; 64; 81; 102
Rated current of electrodynamic withstand of the circuit breaker, kA 32; 51; 64; 80; 102
Rated power of dry transformers for auxiliary needs, kVA 40 4)
No-load current of dry transformers for own needs, A, not more than at voltage 6 kV 0.4
10 kV 0.6
Electrodynamic withstand current of the busbar system and power circuits of the switchgear (amplitude), kA, not less than 2.5Ik
Thermal withstand current flow time, s 3
Input/output execution aerial, cable
Exceeding the heating temperature of accessible switchgear elements above the ambient temperature, °C, no more than 30
Time of localization of an open electric arc within a cabinet or installation unit, s, no more than 0.2
Type of current of auxiliary circuits variable, constant
Nominal voltage of auxiliary circuits, V 380±19; 220±11
Type of grounding system in accordance with the Electrical Installation Code (seventh edition) IT
Frequency of alternating current of auxiliary circuits, Hz 50
Insulation resistance, MOhm 500