Chamber (CELL) KSO-203 UNION
(设备/材料)
描述:
The KCO chambers of the two-hundredth Union series are intended for operation in three-phase alternating current electrical installations with a frequency of 50 and 60 Hz and a voltage of 6 and 10 kV for a system with an isolated or grounded neutral through an arc-suppressing reactor, in conditions of a moderate (U) climate and placement category 3 according to GOST 15150. The KCO Union chambers are used to assemble switchgear RU, which are used to receive and distribute electric power. The operating principle is determined by a set of circuits of the main and auxiliary circuits of the chambers.
概观:
Nominal voltage on the high voltage (HV) side, kV | 6;10 |
Maximum working voltage on the high voltage (HV) side, kV | 7.2; 12 |
Rated current of main circuits, A | 400; 630; 1000; 1600; 2000 |
Rated breaking current of chamber with vacuum circuit breaker, kA | 20; 31.5 |
Rated breaking current of the chamber with a load switch, A | 630 |
Thermal withstand current (3s), | 20; 31.5 |
Nominal voltage of auxiliary circuits, V: AC, DC protection, control and signaling circuits voltage measuring transformer circuits lighting | 220 100 36 |

OOO "Chzeo"
地点: Chelyabinsk region, Chelyabinsk, Lenin Ave., 2, building 3
主要产品/服务: Equipment for electrical networks