添加产品
Product / Equipment

KSO series single-sided Service Prefabricated Chambers

(设备/材料)
状态: New
位置或存放国家: Russia
服务工程支持: Yes
保证: Yes
价钱: 要求价格
描述:
Prefabricated single-sided service chambers of the KSO series (KSO-285, KSO-292, KSO-298, KSO-366, KSO-386, KSO-393), hereinafter referred to as KSO chambers, for a rated voltage of 6 and 10 kV of alternating three-phase current with a frequency of 50 and 60 Hz, intended for distribution devices of networks with neutral isolated or grounded through an arc-quenching reactor and manufactured for the needs of the national economy and for export deliveries.
概观:

The chambers are intended for installation in closed electrical rooms. Climatic version type – UHL according to GOST 15150. The diagrams of the main circuits of the KSO chambers are given in Appendices A, B and C. The overall dimensions of the KSO chambers are given in Appendix G. The list of KSO chamber types is given in Appendix D. The list of devices and equipment required for monitoring and testing of KSO chambers is given in Appendix E. The list of documents referenced in these technical conditions is given in Appendix G.

The structure of the conventional designation of the type of KSO chambers using the example of an input chamber according to the main circuit diagram 5 with a VPMP-10 switch and a PPO-10 drive for a rated current of 600 A has the following form:

KSO-285-5PV-600 UHL3.1, where KSO is a one-way service assembly chamber; 285 is a modification of the chamber (285 – 1985, 292 – 1992, 298 – 1998, 366 – 1966, 386 – 1986, 393 – 1993);

5 – serial number of the main circuit diagram; PV – switch type (PV – VPMP-10 switch with PPO-10 drive; E – VPM-10 switch with PE-11 drive); 600 – rated current of the chamber (400, 600 or 1000 A); UHL3.1 – climatic version and placement category.

By special order, KSO chambers can be manufactured for a lower ambient air temperature of down to minus 45° C, and the order form must be as follows: "KSO-285-5PV-600 UHL3.1, TU 3434-006-971054348-2009, minus 45° C". General requirements - KSO chambers must comply with GOST 14693, the requirements of these technical conditions and a set of design documentation approved in the established manner.

Parameter name KSO-285 KSO-292 KSO-298
Nominal voltage (line), kV 6;10 kV; 6;10 kV; 6;10 kV;
Maximum working voltage (line), kV 7.2; 12.0 7.2; 12.0 7.2; 12.0
Rated current of main circuits (except for KSO chambers with load switches) at a frequency of 50 Hz, A 400; 630; 1000 630; 1000; 1600 630; 1000; 1600
Rated current of the main circuits of the KSO chambers with load switches at a frequency of 50 Hz, A 400 400 400
Rated current of current transformers, A 50; 75; 100; 150; 200; 300; 400; 600; 800; 1000 50; 75; 100; 150; 200; 300; 400; 600; 800; 1000 50; 75; 100; 150; 200; 300; 400; 600; 800; 1000
Nominal current of busbars, A 630; 1000 630; 1000; 1600 630; 1000; 1600
Nominal current of busbar bridges, kA 630; 1000 630; 1000; 1600 630; 1000; 1600
Rated breaking current of high-voltage circuit breaker at 50 Hz, kA 20 20 20
Rated breaking current of load switches at 50 Hz, A 400; 630 400; 630 400; 630
Electrodynamic withstand current, kA 51 51 51
Thermal withstand current, kA 20 20 20

Thermal withstand current flow time, s

for 400 and 600 A chambers

for 1000 and 1600 A chambers

for chambers with load switches


23


1

23


1

23


1

Nominal voltage of auxiliary circuits:

1. Protection, control and signaling circuits of direct and alternating current, V

2. Voltage transformer circuits (protection, measurement, accounting, ATS), V

3. Lighting circuits inside the KSO,V chambers

4. Outside the KSO chambers, B




220



100

36

220





220



100

36

220





220



100

36

220

Maximum current of the power fuse link, A 160 160 160
Maximum speed of load disconnection by automatic drive, ms 3.5 + 0.5 3.5 + 0.5 3.5 + 0.5



Name of parts of KSO chambers Maximum permissible temperature, deg. C
Metal current-carrying parts, except for aluminum and aluminum alloys, in contact with organic insulation or oil. 250
Current-carrying parts made of copper and its alloys that do not come into contact with organic insulation or oil. 300
Current-carrying parts made of aluminum and aluminum alloys. 200





OOO "NZET"

地点: Novosibirsk region, Novosibirsk, Betonnaya st., 8A, building 2
主要产品/服务: Equipment for electrical networks