添加产品
Product / Equipment

Vandal-proof Climate Control Telecommunication Cabinet ST-OU-MTS with hybrid air Conditioner

(设备/材料)
型号编号: ST-OU-MTS
状态: New
位置或存放国家: Russia
服务工程支持: Yes
保证: Yes
价钱: 要求价格
描述:
Vandal-proof climatic telecommunication cabinet, designed to accommodate and operate communication equipment (3G/4G base station, ⎓-48V power supply, batteries, radio relay equipment, cross and optical equipment) of the 19” standard in the amount of 27U and maintain the required temperature and humidity conditions. The cabinet has space for placing 1 group of front-terminal lead-acid batteries with a capacity of up to 190 Ah or lithium-ion batteries with a capacity of up to 100 Ah. The cabinet is equipped with an input-distribution panel for 2 inputs ~230/400 V, optionally a bidirectional multi-tariff meter with the ability to integrate into the AMR system and an ATS controller can be installed. The design of the cabinet provides a degree of protection against moisture and dust of at least IP55. To ensure the maintenance of the required climatic conditions, the cabinet can be equipped with: an air conditioner, a heat exchanger, fans and a heating element. A combination of different climate control equipment is possible.
概观:
Indicators Quantities
Overall dimensions W x D x H In accordance with the table of standard designs
Weight of cabinet without equipment In accordance with the table of standard designs
Thickness of outer steel sheet 2mm
Climate type design UHL1, (optional O1)
Operating temperature range -40 ÷ +50°C
Degree of protection IP55
Number of units for equipment
  • ST-OU-MTS-1-K-19 - 27U*
  • ST-OU-MTS-1.1-K-19 - 37U*
  • ST-OU-MTS-3-K-19 - 20U*
  • ST-OU-MTS-5-K-19 - 12U*
  • ST-OU-MTS-6.1-V-19 -4U
  • ST-OU-MTS-6.2-V-19 -2U *
  • Depending on the configuration and design, the cabinet's own equipment can occupy from 2 to 5U
Thermal conductivity coefficient of insulation λ not less than 0.037 W/(m2 K)
Insulation flammability class NG
Distance from front panels to door not less than 100mm
Ventilated space under the roof 50mm
LED light ⎓48V Yes
Lock resistance class 4
Plinth height 200mm
Color of the body coating RAL7035
Verkhovna Rada of Ukraine
Number of power inputs 2 ("NETWORK" and "DGU")
Supply voltage 3F ~400V (phase-by-phase ~230V±10%) 3L+N+PE
Introductory AB 32A characteristic “C”
Input AB DGU 32A characteristic “C”
SPD of input circuits II+III (Level C+D) Inom=20kA or I+II (Level B+C) Iimp=12.5kA
RCD 16A characteristic "C", leakage current 30mA
Service socket 1F ~230V 16A
Voltage distribution unit on the EPU 3АВ 1п for each phase
Counter optional CE303
Main ground busbar Yes, 8 connections for M6 screw
External ground bolt Yes, M8
Climate system
Internal temperature range provided by the SCS
  • air conditioner +5 ÷ +35°C
  • ventilation +5 ÷ +55°C
Power of the SCV 0.6/0.8/1.0/1.3/2.0/2.5/3.0 kW depending on the KSh configuration
Thermosiphon power (with hybrid design of the SVC) not worse than 110W/K
Noise level no more than 55 dB(A)
Power supply for SKV fans ⎓-48V
Disabling the SCS on fire/open door signal Yes
Compressor motor resource Not less than 70,000 hours
Fan motor resource Not less than 50,000 hours
EPU
Power of the EPU 6, 9, 12, 15, 18 kW
Input voltage range of rectifier power supply ~85÷300V, ⎓ 95÷270V - without reducing output power ~176÷300V, ⎓ 190÷270V
Efficiency of rectifiers > 95.5%
Element-by-element control of the battery Yes
Place for battery group 1 group with capacity up to 190 Ah
Number of battery groups to connect 1, 2 or 4
Load contactors 3 lines (BLVD+LLVD1+LLVD2)
Monitoring/control channels SNMP v. 1/2/2c/3 Wi-Fi GSM/3G/4G Web interface USB port (Host)
Alarm sensor inputs flooding, door, fire, impact, filter, humidity, temperature
Number of digital inputs 6
Number of relay outputs 8
Efficiency Manager Yes
Load distribution
3U high panels 48 load lines AB from 2 to 125A characteristic "C" 10kA Configuration is specified when ordering

JSC "Energomera"

地点: 355035, Russia, Stavropol, Lenina St. 415, office 294
主要产品/服务: Equipment for electrical networks